Applications
Machine tools
Hydraulics and pneumatics
Automation engineering
Special-purpose machine building
Special features
Industry 4.0-ready IO-Link sensor improves connectivity and diagnostics
Designed for rough demands of up to 1,000 g shock and -40 ... +125 °C [-40 ... +257 °F]
Optimised design makes OEM machine integration easier
Multicolour 360° LED status display simplifies troubleshooting and localisation
The given measuring ranges are also available in kg/cm², kPa and MPa.
Special measuring ranges between 0 ... 0.4 and 0 ... 1,000 bar [0 ... 10 to 0 ... 15,000 psi] are available on request.
Special measuring ranges have a reduced long-term stability and higher temperature errors.
Overload safety
The overload safety is based on the sensor element used. Dependent on the selected process connection and the sealing, restrictions in overload safety can result.
Measuring range ≤ 600 bar [< 8,000 psi]: 2 times
Measuring range > 1.000 bar [≥ 8,000 psi]: 1.5 times
Increased overload safety (option)
With increased overload safety there are deviations in temperature error and long-term stability.
Vacuum-tight
Yes
LED status display (option)
Visibility: 360°
Green: Operation
Yellow: Warning
Red: Error
IO-Link
Revision: 1.1
Transmission rate: 38.4 kBaud (COM2)
Min. cycle time: 2.3 ms
Master port class: A
Adjustment of zero point offset
max. 3 % of span (via IO-Link)
Damping of switching outputs
0 ms ... 65 s (adjustable via IO-Link)
Switch-on time
1 s
Switching thresholds
Switch point 1 and switch point 2 are individually adjustable via IO-Link.
Switch point 1 can be set to the prevailing pressure value using the teach function.
Switching functions
Normally open, normally closed, window, hysteresis (adjustable via IO-Link)
The switching function of switch point 1 can be set to normally closed or normally open using the teach function.
Switching voltage
Power supply - 1 V
Switching current
max. 250 mA, see derating curves
Response time of switching output
≤ 5 ms
Service life
100 million switching cycles
Voltage supply
Power supply
DC 10 ... 32 V
Current consumption
≤ 25 mA
Total current consumption
≤ 0.3 A incl. switching current (with one switching output)
≤ 0.6 A incl. switching current (with two switching outputs)
Reference conditions (per IEC 61298-1)
Temperature: 15 ... 25 °C [59 ... 77 °F]
Atmospheric pressure: 860 ... 1,060 mbar [12.5 ... 15.4 psi]
Air humidity: 45 ... 75 % r. h.
Nominal position: Calibrated in vertical mounting position with process connection
facing downwards.
Power supply: DC 24 V
Accuracy, switching output
≤ ±1 % of span (option: ≤ ±0.5 % of span)
Long-term drift, switching output
≤ ±0.1 %
≤ ±0.2 % for measuring ranges ≤ 0.69 bar [10 psi]
≤ ±0.26 % for increased overload safety
Switching current dependency
With switching currents greater than 50 mA:
≤ ±0.05 % per 50 mA additional applied switching current
Versions without teach function, LED status display and
IO-Link 1.1:
≤ ±0.075 % per 50 mA additional applied switching current
Temperature error in rated temperature range
≤ ±1.5 % of span
≤ ±2.5 % of span for increased overload safety
Temperature coefficients in rated temperature range
Mean TC zero point: ≤ ±0.16 % of span/10 K
Mean TC span: ≤ ±0.16 % of span/10 K
Humidity
45 ... 75 % r. h.
Vibration resistance
25 g, 10 ... 2,000 Hz (IEC 60068-2-6, under resonance)
Shock resistance
100 g, 6 ms (IEC 60068-2-27, mechanical)
1,000 g, 1 ms (IEC 60068-2-27, mechanical) 1)
Service life
100 million load cycles
Ingress protection (per IEC 60529)
see “Electrical connections”
Mounting position
as required