Application and function
The temperature transmitter LI-24ALW is applicable to converting resistance of temperature or voltage of thermocouple sensor to standard current signal 4-20mA. The transmitter has two separate channels enabling measurement of temperature difference, averange, averange with redundancy, max. or min. temperature. Transmitter has compensation of ambient temparature influence and compensation of thermocouple cold junction using internal/external (Pt100) sensor or constant temperature. Most of parameters such as: sensor type, measuring range, current alarm signal when electric circuit is broken, output characteristic correction, user characteristic (60 points) are programmed using PC with HART/USB converter and Aplisens RAPORT 2 configuration software. For request Aplisens can set temperature transmitter parameters like measuring range, type of sensor. Their values are printed on label. Transmitter LI-24/ALWis designed for field use. LI-24ALWcan be used with temprature sensors mounted directly in transmitter’s casing or with external sensors connected with cable.
Technical data
Input signal
Resistance: Pt100,Ni100
Voltage: K, J,S,B,N,T, R, E
Limit process
-10mV< E<100mV or -100mV< E<1000mV
0W
Min. measuring range 10mV or 10W or 10K
Output signal 4 - 20 mA + Hart
Power supply
13,5*…55 VDC
Exia: 13,5*…30 VDC
Exd: 13,5*…45 VDC
Safety, Safety Exd: 12,5…36 VDC
Safety Exia: 12,5…30 VDC
Ambient temperature:
-40…+80°C
Exia: -40…+80°C
Exd: -40…+75°C
Safety: -40…+85°C
Safety Exia, Safety Exd: -40…+75°C